Rural Electrification with the Shield Wire Scheme in Low-Income Countries : Design, Construction, and Operation

The manual begins with a description of the concept and aims of the shield wire scheme (SWS). The scheme is applicable for minimum cost power supply from the grid to villages, small towns, farms, factories, and water pumping stations located near o...

Full description

Bibliographic Details
Main Author: Iliceto, Francesco
Language:English
en_US
Published: World Bank, Washington, DC 2017
Subjects:
Online Access:http://documents.worldbank.org/curated/en/500631493652099113/Rural-electrification-with-the-shield-wire-scheme-in-low-income-countries-design-construction-and-operation
http://hdl.handle.net/10986/26647
Description
Summary:The manual begins with a description of the concept and aims of the shield wire scheme (SWS). The scheme is applicable for minimum cost power supply from the grid to villages, small towns, farms, factories, and water pumping stations located near or at some distance from the route of the high-voltage (HV), 110 to 330 kV, transmission lines (TLs). The SWS is a solution for rural electrification that is not economically justifiable with conventional solutions, which are long medium-voltage (MV) lines routed along the HV TLs or dedicated HV/MV transformer stations. SWSs consist of the following: Insulating the shield wires (SWs) from the towers of the HV TL for MV operation (20 to 34.5 kV). Energizing the SWs at MV from the HV/MV transformer station at one end of the HV TL. Using the earth return of current as an MV distribution conductor. Supplying the loads by means of medium-voltage/low-voltage (MV/LV) distribution transformers connected between the SWs and the ground.